System Evacuation

Before adding refrigerant charge, evacuate to proper vacuum level to remove non-condensable gases and to evaporate and remove moisture in the system.
This chart shows the vacuum level and the temperature at which water will vaporize.
Pressure Vacuum Equivalents
Absolute pressure
above a zero base
Vacuum below
one atmosphere
Fraction
of one
atmosphere
Vaporization
temperature
of H2O in °F
Microns
PSIA
mm Hg
Inches Hg
0
0.000
760.00
29.921
-
-
50
0.001
759.95
29.920
1/15000
-50
100
0.002
759.90
29.920
1/7600
-40
150
0.003
759.85
29.920
1/5100
-33
200
0.004
759.80
29.910
1/3800
-28
300
0.006
759.70
29.910
1/2500
-21
500
0.009
759.50
29.900
1/1500
-12
1,000
0.019
759.00
29.880
1/760
1
2,000
0.039
758.00
29.840
1/380
15
4,000
0.078
756.00
29.760
1/190
29
6,000
0.117
754.00
29.690
1/127
39
10,000
0.193
750.00
29.530
1/76
52
15,000
0.290
745.00
29.330
1/50
63
20,000
0.387
740.00
29.130
1/38
72
30,000
0.580
730.00
28.740
1/25
84
50,000
0.967
710.00
27.950
1/15
101
100,000
1.930
660.00
25.980
2/15
125
200,000
3.870
560.00
22.050
1/4
152
500,000
9.670
260.00
10.240
2/3
192
760,000
14.696
0.00
0.00
1 atmos
212